Page 1 - FAAC 746 & 844

FAAC 746 & 844SLIDING GATE AUTOMATIONWITH CP81 CONTROLLERINSTALLATIONMANUALLatest Revision: 05.04.2004Document Ref.: 1074.D.01.0001_4

Page 2

CONSULT THE ADJACENT TABLE TO DETERMINE THE CORRECT GATE WHEEL ROOT SIZE AND ROUND BAR TRACK DIAMETER REQUIRED IN RESPECT OF GATE MASS AND DUTY.GATE

Page 3 - Table of Contents

400mm90155GATEWALL0 to 5044MOTOR MOUNTED RHS(VIEWED FROM INSIDE PROPERTY)225GATEWALLBASEPLATE0 to 509044MOTOR MOUNTED LHS(VIEWED FROM INSIDE PROPERTY)

Page 4 - 1. PRODUCT TECHNICAL DETAILS

102.4.3 ACCESSING CONTROLLER MODULE2.4.4 POSITIONING GEARBOXlOpen up cover of operator to allow easy access in order to feed in main supply and signal

Page 5 - 1.2 TECHNICAL SPECIFICATIONS

213±350 mm2.4.6 MOUNTING OF RACK11lAttach steel rack to gate using the 25x25x2mm angle brackets (1) supplied, spaced approximately 350mm apart.lDistan

Page 6 - 2. PRODUCT INSTALLATION

JOINING STEEL RACKWELD HEREN.B. DO NOT WELD NEAR MESHING SURFACESRACK MUST BE LEVEL200 - 300mm RACK OFFCUTMOUNTING and JOININGof NYLON RACK (RA

Page 7 - 2.2 CABLE REQUIREMENTS

2.4.7 MOUNTING AND POSITIONING LIMIT SWITCH PLATES13lThe FAAC 746 & 844 operators are fitted with an inductive proximity limit switch (1). When th

Page 8 - 2.3 GATE REQUIREMENTS

3. ELECTRICAL CONNECTIONSN.B.1) FOR SINGLE PHASE FAAC 746/844 MOTORS THE CP81 CONTROLLER COMBINED WITH THE CP89 POWER SUPPLY BOARD IS USED;

Page 9

15POWER WIRING DIAGRAM FOR 1 MOTOR (746 / 844)CENTURION CP89POWER SUPPLY PCB220V ACINPUT SUPPLYREDBLACKM1, M3 CABLES MAY NEEDREVERSAL DEPENDING ONRE

Page 10 - 2.4 UNIT INSTALLATION

LSLS16POWER WIRING DIAGRAM FOR 3 MOTOR (844 3 PHASE)CENTURIONCP89INTERFACE PCBSEPARATE WEATHERPROOF ENCLOSURE OPERATOR MOUNTEDENCLOSURE4LINE 1LINE

Page 11 - POSITIONING

SAFETY BEAMBEAMIRB+12VLINKNOTE - TYPICAL SAFETY BEAM IS SHOWN. REFER TO MANUFACTURER FOR DETAILSN.B. IF BEAMS ARE NOT USED THEN ENSURE THA

Page 13 - USEFUL TIP

NOTE:INTERCOM CONNECTIONSEXAMPLE 2 BPT 1 - 1 (WITH 12V DC POWER SUPPLY)COMMAX 1 - 1 (12V)TYPICAL 220V AC POWERED INTERCOMTEGUI 12V DC INTERCOMEXAMPLE

Page 14 - MOUNTING and JOINING

SIGNAL COMMON0,2mmCABLE2CONTROLLERMODELCP81 LEDCOMREMOTE GATE STATUS LIGHT EMITTING DIODE (LED)COMLEDFITTED TO HANDSET BASE SEPARATELYSTATUS LEDANODE

Page 15

0,2mmCABLE2CONTROLLERMODEL2 POSITION SWITCHCP81 12V LCK COMHOLIDAY LOCKOUTORORPUSHBUTTONKEYPADNB: IF HOLIDAY LOCKOUT IS NOT USED, ENSURE THAT A LINK I

Page 16 - 3. ELECTRICAL CONNECTIONS

LD 100 OR 101 INDUCTIVE LOOP DETECTOR IS SHOWN BELOW.MODIFY WIRING IF OTHER MAKES OF DETECTORS ARE USED.FREE EXIT LOOP -0,2mmCABLE2CONTROLLERMODELCP81

Page 17 - FAAC V1.XX

LOOP DETAILS- WIRE: 1.5mm SQUARED MULTI STRANDED CABLE (USE SILICON COATED IF PLACED DIRECTLY INTO THE GROUND)- SPACING BETWEEN TWO ADJACENT LOOPS &g

Page 18 - CP81 PCB

1,5mm CABLE2TRANSFORMER POWER SUPPLYCP89 cardin motor enclosureCP89 POWER SUPPLYCP81control cardTO CP81CONTROLLERTO FAACTERMINATIONBOARD12V DC SUPPLY

Page 19 - SAFETY BEAM

15mmA/F5mm4. COMMISSIONING PROCEDURE4.2 ADJUSTMENT OF ANTI - CRUSHING SYSTEM4.1 REMOVE OIL BLEED SCREW (IMPORTANT)The 746 & 844 automation systems

Page 20 - EXAMPLE 4

xxCP81CONTROLLERGREENPOWER ON12V DC SUPPLY TOCP81 CONTROLLERTO FAACTERMINATIONCARDLIMIT SWITCHCABLE TO CP81TO CP81CONTROLLERL N220V ACSUPPLYE4.3 APPLY

Page 21 - PEDESTRIAN KEYSWITCH

N.B. Procedure 1 and 2 MUST be performed on initial commissioning. Procedure 3 to 5 are required ONLY if the default settings on the

Page 22 - HOLIDAY LOCKOUT

Check if limit switch wiring is correct for one of thealternatives shown belowSTATUS LED must go OFF when gate is in closed position and stopplate is

Page 23 - See details A & B

11. PRODUCT TECHNICAL DETAILS . . . . . . . . . . . . . . . . . . . . . 21.1 DIMENSIONS...21.2 TECHNICAL SPECIFICATIONS . .

Page 24 - (Recommended

If Step 1 is incorrect then swop limit switch polarity as shown below:Motors fitted with FAAC termination board(See Page 15 for wiring diagram)Motors

Page 25 - TRANSFORMER POWER SUPPLY

N.B. If direction is incorrect Stop Motor (or Remove Power) IMMEDIATELY, or serious damage could be done if gate runs into an End Stop.- Make s

Page 26 - 4. COMMISSIONING PROCEDURE

Remove the electronics power from the PCB.All LED' s will extinguish.Fit SET link to PCB.Reapply power ( Reversal of STEP 1 above ). Check th

Page 27 - 4.3 APPLYING MAINS POWER

Ensure that PCB is in PROGRAMME MODE i.e. LED, L 2,MUST be illuminated (if not refer Procedure 3 ).Hold TEST P/B DOWN until LED, L 1, flashes the requ

Page 28

Press & Hold TEST button while monitoring STATUS LED;Release the Pushbutton after STATUS LED Flashes the required number of times to select the re

Page 29 - Striker Plate

TABLE 5.1Ensure that PCB is in PROGRAMME MODE i.e. LED, L 2,MUST be illuminated (if not refer Procedure 3).Hold TEST P/B DOWN until number of flashes

Page 30 - OPTION 2

Press and Hold TEST button while counting the number oftimes STATUS LED flashes;Release the Pushbutton when the flashes count = time(or count ) requir

Page 31 - PROCEDURE 2

1. REMOVE POWER.2. FIT THE "SET" LINK.3. CONNECT "PED" AND "FRX" TO "COM".4. RECONNECT POWER. L1 AND L2 WILL I

Page 32

5. MANUAL OPERATIONShould the need arise to operate the gate manually because of power failure or malfunction, release it by operating the releasing s

Page 33 - TABLE 4.1

6. MAINTENANCE7. REPAIRSOIL LEVELPeriodically check the oil level. For medium to low duty cycles, it is advisable to perform the check annually. Where

Page 34 - TABLE 4.2

BAC1. PRODUCT TECHNICAL DETAILSTHE FAAC 746 & 844 GATE OPERATORS ARE SELF-CONTAINED UNITS CONSISTING OF A WORMGEARED ELECTRIC MOTOR , AN ELECTRONI

Page 35 - - SETTING DURATION OF TIMERS

CENTURIONTHE AUTOMATIC CHOICE CENTURION SYSTEMS (PTY) LTD HEAD OFFICE:TEL: +27 (0)11 699-2400, FAX: +27 (0)11 704-3412 or 462-6669 148 EPSOM AVENUE, N

Page 36

1.2 TECHNICAL SPECIFICATIONSMODEL 746 844 844 3 PHASEPOWER SUPPLY 230V~ (+6% - 10%) 50Hz 230V~ (+6% - 10%) 50Hz 380V, 3 Phase 4 wire availableABSORBED

Page 37 - 4.5 TESTING THE AUTOMATION

2.1 RECOMMENDED TOOLS2. PRODUCT INSTALLATIONSTEEL BITS, 3 - 12mmFLAT and RINGSPANNER8, 10, 13, 17 & 19mmSCREW DRIVER5mm FLATNo 1. PHILLIPSCRIMPIN

Page 38 - 5. MANUAL OPERATION

2.2 CABLE REQUIREMENTSG.P. = GENERAL PURPOSE HOUSE WIRING OR PANEL FLEXS.W.A. = STEEL WIRE ARMOUREDn1 = CONSULT INTERCOM SUPPLIER FOR RE

Page 39 - 7. REPAIRS

2.3 GATE REQUIREMENTSIt is important to ensure that the motor is capable of moving the gate as required. Duty cycle must be considered:MAXIMUM DUTY CY

Page 40

ENSURE THAT THE GATE IS FITTED WITH CORRECT END STOPS, ETC.AS SHOWN IN THE SKETCHES BELOW.NOTE 1: The Bottom of the Round Bar (T Bar or Channel Iron